How the models work · Wall heat model

8. Working out the results

Surface temperatures and heat flow

Slice temperatures are at slice centres. The face temperatures are found by balancing the heat flow across half a slice with the heat flow across the surface film on that side, which sets the surface temperature between the slice centre and the air temperature on that side. The heat flow into the room is:

q = (Tinner face − Troom) ÷ Rsi (negative values are flowing out of the room)

U-value

The U-value is calculated directly, as 1 ÷ the sum of all layer resistances and the two surface films, as explained above. It is not the result of the simulation. With a ventilated gap, the path through the layers outside the gap runs in parallel with the gap's direct link to outdoor air, and the U-value is worked out from that combination.

Decrement factor and delay

A day-long cycle can be broken into a simple, once-a-day cosine wave (its first harmonic) plus faster ripples. The tool fits that daily wave to both the sol-air temperature and the heat flow at the inner face, using a discrete Fourier sum, and compares them:

decrement factor = (amplitude of inner heat flow) ÷ (U × amplitude of sol-air temperature)
decrement delay = how many hours the inner heat-flow wave peaks after the sol-air wave

The denominator is the swing in heat flow you would get with no thermal mass at all, so the ratio says how much of that swing survives.

Steady-state comparison

The dashed line in the heat-flow chart is U × (sol-air − room temperature), calculated for each moment. It is the answer a simple U-value calculation would give, with no delay and no storage, from exactly the same outside and room temperatures.

Energy totals

The positive and negative parts of the heat flow are added up separately over the 24 hours to give the Wh/m² gained and lost, and the day's sunshine is added up in kWh/m².

Thermal mass figures

The inner thermal mass is the areal heat capacity of BS EN ISO 13786: how much heat a square metre takes in and gives back when the room swings over a 24-hour cycle. Each layer's conductivity, density and heat capacity set how far the swing reaches into it, about 100 mm into brick or stone but hardly past insulation. Mass behind insulation drops out, and low-conductivity layers that hold heat, such as wood fibre, count in part, so the tool needs no rule about which layer is the insulation. The room-side surface film is left out, because the house runs model that link separately. The whole-wall figure simply totals every layer. The house runs add up the same figure over every wall, floor and ceiling of a room to get its thermal mass, treating the room as empty. A wall or floor between two rooms counts half to each.

Colours and arrows

The colour scale is symmetrical about the average room temperature, wide enough to hold the hottest and coldest slice temperatures of the day (and never less than ±2 K). The arrows are the heat flow across each cell boundary, scaled against the largest flow found anywhere in the wall over the day.