Floor edges and junctions
A floor on the ground doesn't lose heat evenly. Heat leaving the middle of the floor has to travel down and out through metres of soil before it reaches the outside air, so very little goes that way. Near the edge the path is short: down a little, sideways under the wall, and up to the ground outside. Most of a ground floor's heat loss leaves through a band a metre or two wide round its perimeter.
That is why a small floor loses more per square metre than a big one: more of it is close to an edge. BS EN ISO 13370, the standard the planner uses for ground floors, captures this with the floor's characteristic dimension B′, its area divided by half its exposed perimeter. The smaller B′, the higher the U-value for the same build-up.
The foot of an outside wall in the example house: the wall on its foundation, the floor build-up beside it, the ground, and (dashed) heat slipping round the edge of the floor insulation into the wall.
Edge insulation
Because the edge matters so much, insulating just the edge helps. Horizontal edge insulation is a band laid flat at the slab edge, running out from the wall (outside, under the ground) or in from it (under the slab). Verticaledge insulation runs down the face of the foundation, outside or inside. Either way it makes the heat's path to the outside longer. A vertical strip is worth about a horizontal one twice as wide, because heat has to go down and back up round it: 0.5 m down does about as much as 1 m out. It helps most on small or poorly insulated floors.
The floor-to-wall junction
Where the floor meets the wall there is a second leak. The floor's insulation stops at the wall, and the wall's insulation stops at the floor, so heat can slip round both: from the warm screed into the inner leaf of the wall, down into the foundation and out. This is a thermal bridge, and it is counted separately from the U-values as a linear thermal transmittance, Ψ (psi): the extra heat lost per metre of wall for each degree of temperature difference, in W/mK.
It adds up. A house with 30 m of outside wall and Ψ = 0.32 W/mK (SAP's figure for an unchecked detail) loses about 10 W per degree through that junction alone: on a cold day, as much as a couple of square metres of window. In a well-insulated house junctions can be a fifth or more of the whole floor's loss.
- A perimeter upstand, a strip of insulation standing on edge between the floor screed and the wall, breaks the path and roughly halves Ψ in a typical cavity-wall house.
- The foundation matters too. Dense concrete or stone under the wall conducts heat round the floor insulation; an aircrete block or a deeper, insulated foundation slows it.
- Old houses often have shallow brick or stone footings, or none at all, with the wall standing almost on the ground. That gives heat a short, conductive route out, and changes Ψ a lot.
Set all of this on the Floors page. How the junction Ψ is worked out explains the calculation.