Control plans, zones and cooling
A wet heating system has one heat source and many places the water could go: radiators or underfloor loops in each room, and the coil in a hot water cylinder. Motorised valves, opened and shut by room and cylinder thermostats through a wiring centre, decide which of those get water. A handful of standard layouts cover most UK homes.
- Y plan. One 3-port mid-position valve where the heating and hot water pipes split. Port A feeds the cylinder, port B the heating, and the mid position feeds both. Cheap and common with boilers. When both are called, the water is shared, so neither gets the boiler's full output.
- S plan. Two 2-port zone valves, one on the heating and one on the cylinder, each opened by its own thermostat. Either, both or neither can be open.
- S plan plus. An S plan with a 2-port zone valve for each heating zone (say living areas, bedrooms and bathroom), so each zone runs on its own thermostat and timer. This is what zoning usually means.
- W plan. A 3-port diverter: the water goes to the heating or to the cylinder, never both. Hot water has priority: the heating pauses while the cylinder reheats.
- Heat pump. Nearly always a diverter with hot water priority, because the cylinder needs a much hotter flow (around 50 to 55 °C) than the heating (35 to 45 °C). A heat pump runs most efficiently at the lowest flow it can, so it serves one at a time. Zone valves are added where there are zones, and isolation valves where it cools.
- Combi. No cylinder: the boiler heats tap water as it flows, through a plate heat exchanger, with a diverter inside the boiler. Heating pauses while a tap runs.
Why priority matters for pipe sizes
Pipes are sized for the most water they ever carry. With no valves, or a Y or S plan calling both at once, the primary pipe from the source carries the heating and the cylinder reheat together. With priority it carries one or the other, so it is sized for the larger. The planner works the flows out mode by mode and sizes each run for its busiest. It also finds the index circuit (the path with the highest pressure drop, which the pump must overcome) in each mode and checks the worst one against the pump.
Zones and the pump
When every zone valve is shut but the pump still runs, it pushes against closed valves. That is noisy, and it can starve a heat pump of the minimum flow it needs. The usual fixes are an automatic bypass valve, a buffer tank, or wiring that stops the pump when no zone calls. The planner flags any mode where every circuit is shut.
Cooling with a heat pump
A reversible heat pump runs its refrigerant cycle backwards and sends chilled water, typically 15 to 20 °C, round the same pipes. How well that cools depends on the emitter:
- Underfloor loops cool gently. Cold air sits low, so a cool floor transfers heat less well than a warm one: the planner takes about 60% of the heating coefficient. More importantly, the floor surface must stay above the dew point of the room air, or water condenses on it. At 25 °C and 60% humidity that is about 17 °C, and EN 1264 also keeps occupied floors at 19 °C or more. That limits a floor to roughly 30 to 45 W/m².
- Fan coils blow room air over a coil, so they cool and heat well. Their output is close to proportional to the difference between the water and the air. Colder water cools much more, but then the coil condenses moisture and needs a drain. The planner counts their sensible cooling only (the air temperature, not the drying).
- Radiators and towel rails barely cool. Below the dew point they sweat and drip. A cooling system shuts them off with isolation valves while it cools. The Heat pump plan adds those valves, and the checks flag any radiator left on chilled water.
Cooling efficiency is the EER (energy efficiency ratio): heat taken out per unit of electricity. It is rated at 35 °C outside and 18 °C water, and gets better as it gets cooler outside, since the heat pump has less far to lift the heat. The planner takes about 2.5% better for each degree cooler, between half and 1.6 times the rated EER. In the runs, a heat pump that is heating in an hour does not also cool in that hour.