How the models work · Moisture model

7. Working out the results

Water held and the verdict

"Liquid water held" in a layer is the water above what it would hold at 95% humidity, added up over its slices, at the end of each month. Hygroscopic moisture below that level is normal and is not counted. Stays dry if the total never reaches 5 g/m² in the final year. Gets wet, then dries out if it does, but at some month end (the wall's driest point, often summer, before autumn rain starts again) every layer is dry again: under 5 g/m², or under a tenth of the water it could hold above 95% humidity, whichever is more. The tenth is a judgement call so that thick masonry, which in a wet climate always keeps a little water in its outer part, is judged against its own size: for a thin board the limit is still 5 g/m², for 500 mm of stone it is several kilograms. A wall that has still not settled after twelve years, its driest month wetter than the year before's, gets wetter year on year, however little it holds yet. Otherwise it stays damp all year. The peak is the largest month-end total, and the layer named is the one holding most of it then.

Settled state

Following WTA 6-5, the wall has settled once the water in every layer, and in the wall as a whole, changes by less than 1% from the same date a year before. Results come from the year after that. A wall still changing after twelve years, with its driest month wetter than the year before's, is reported as getting wetter year on year.

Frost

The part of each masonry layer that can freeze is found from the steady temperatures on a −5 °C night. Through November to March, the water in that part is compared with its open pore volume. WTA 6-5 allows masonry of unknown frost resistance to fill 30% of its pores, about half the saturation at which frost damage usually starts, or more if the humidity there stays under 95%. The model has no porosity data, so open porosity is estimated from free saturation, which typically fills about three quarters of the pores (164 sandstones average 0.71; ASTM C216 caps brick at 0.78).

The simulation takes the wall to be in good condition. A sound existing wall has already shown it survives its own winters, so going over 30% only counts as a frost risk where insulation makes the freezing zone wetter than the same wall without it. That before-and-after comparison is how internal insulation is normally judged for frost (WTA 6-5; Straube and Mensinga). For the comparison, insulation lining the wall is taken off, and a filled cavity goes back to an empty one.

Behind internal insulation

Where insulation is fixed inside masonry, with only thin finishes on the room side, the peak monthly humidity where the two meet is graded as WTA 6-5 does. Up to 95% suits any materials. 95–99% suits only materials that tolerate damp, frost and rot: mineral layers such as lime, insulating plaster, mineral board and stone do, while timber and fibre, gypsum and foam boards are flagged. Over 99%, condensation can form and the system needs a full design study.

Gypsum

A gypsum plaster or plasterboard layer is flagged if its humidity goes over 95% at either face (WTA 6-5), as gypsum loses strength when damp.

Rot

For each organic layer, the moisture content by mass is averaged over the 10 mm at each face, every step of the final year, and the higher peak is compared with 18%.

Mould

The inner surface humidity is the room's vapour pressure divided by the saturation pressure at the inner surface's temperature, from the monthly mean temperatures. Months above 80% are flagged. For this check only, the inside film is taken as 0.25 m²K/W, as ISO 13788 sets for walls and roofs. That allows for the colder spots in corners and behind furniture, where mould usually starts.

Pressure line and flow arrows

The pressure chart shows monthly averages at each layer boundary. Each layer's arrow is the vapour and liquid flow together, through the middle of the layer, averaged over the month and converted to grams per square metre per day, positive towards the inside. Arrow thickness and darkness are in proportion to the flow, with 50 g/m² per day or more drawn at full width, so a layer passing a tenth as much shows a tenth the arrow. Hover over an arrow for its figure.

Animation

When you move to another month, every number on the pressure chart is eased from the old value to the new one over about half a second. The easing is only for show: the whole simulation is run once, up front.