The ground floor and its edge

Each ground-floor room's floor U-value comes from BS EN ISO 13370. For a slab on the ground it depends on the floor build-up's resistance Rf, the soil's conductivity λ (2.0 W/mK for clay or silt, the standard's default), the wall thickness w (taken as 0.3 m) and the house's characteristic dimension B′:

B′ = floor area ÷ (½ × exposed perimeter) dt = w + λ (Rsi + Rf + Rse)
U = 2λ ÷ (πB′ + dt) × ln(πB′ ÷ dt + 1) when dt < B′, else U = λ ÷ (0.457 B′ + dt)

Foundation edge insulation of width (or depth) D and resistance R′ lowers that by a further term from the same standard, with a vertical strip counted as 2D. Suspended timber floors use the standard's suspended-floor method instead: the deck in series with the ground under the void, the void's walls and its airbrick ventilation.

The floor-to-wall junction is then added on top: Ψ × each room's outside wall length on the ground floor, shared over its floor area. Ψ is SAP's default (0.32 W/mK), its approved-detail figure (0.16), your own, or calculated as described next.