The ground floor and its edge
Each ground-floor room's floor U-value comes from BS EN ISO 13370. For a slab on the ground it depends on the floor build-up's resistance Rf, the soil's conductivity λ (2.0 W/mK for clay or silt, the standard's default), the wall thickness w (taken as 0.3 m) and the house's characteristic dimension B′:
Foundation edge insulation of width (or depth) D and resistance R′ lowers that by a further term from the same standard, with a vertical strip counted as 2D. Suspended timber floors use the standard's suspended-floor method instead: the deck in series with the ground under the void, the void's walls and its airbrick ventilation.
The floor-to-wall junction is then added on top: Ψ × each room's outside wall length on the ground floor, shared over its floor area. Ψ is SAP's default (0.32 W/mK), its approved-detail figure (0.16), your own, or calculated as described next.