2. Slices, heat and vapour
Each layer is cut into slices 2 mm thick at both of its faces, growing by 60% at a time to at most 20 mm in its middle, because the sharpest changes happen at faces and boundaries. An air cavity is a single slice with its own thermal resistance. If the build-up has a ventilated gap (a roof tile batten void, for instance), everything outside it is at outdoor conditions, so the analysis starts at the inner face of the gap.
Heat flows between slices as on the heat tab, with surface films of 0.04 m²K/W outside and 0.13 inside (0.10 for a roof). Two things differ. Water conducts heat, so a wet material conducts more, by the usual allowance of 8% per percent of moisture by mass:
And water condensing in a slice releases 2.5 MJ per kg, which evaporation takes back, so a drying face is cooled by its own evaporation.
Vapour flows between slices by diffusion, from high vapour pressure to low:
Each slice's µ moves smoothly from the material's dry-cup value at 50% humidity to its wet-cup value at 90%, because hygroscopic materials let vapour through more freely when damp. At the faces, vapour passes to the air through a surface film, worked out from the convective heat transfer by the standard Lewis relation.