InsuliserBeta
Concepts · Heat

Decrement factor and delay

When the outside temperature rises and falls over a day, a wall with thermal mass does two things to that rhythm. It makes the swing smaller and it makes it arrive later. Engineers give these two effects names:

  • Decrement factor (between 0 and 1): the fraction of the outside heat swing that still shows up at the inner face. 0.3 means only 30% gets through. Lower is better in summer.
  • Decrement delay (in hours): the delay between the outside peak and the peak of heat flow at the inner face. You will also see this called "time lag". A decrement delay of 8 hours means the heat from a 3 pm peak arrives at 11 pm.
00:0006:0012:0018:0024:00decrement delaydampedoutsideinside
Schematic only. A heavy, well-insulated wall turns a big, early swing outside (orange) into a small, late one inside (blue).

Compare this to a steady-state calculation, which has no memory and no delay. It would say the heat flow follows the outside temperature instantly. The chart called Heat flow into the room shows both: the dashed grey line is the steady-state estimate, and the blue line is what the simulation produces once thermal mass is accounted for.

Good insulation and good thermal mass do different jobs. Insulation (a low U-value) shrinks the overall flow. Mass shrinks and shifts the daily swing in that flow. A wall can be strong at one and weak at the other, which is why this tool shows both.

The decrement factor is a share of the swing the wall would pass with no mass, which is U × the outside swing. So the swing that actually reaches the room is decrement factor × U × the outside swing. A lightweight, well-insulated wall can have a high decrement factor and still pass only a small swing, because its U-value is small. Compare the heat-flow chart, not the factor alone, when U-values differ a lot.